Catalog pricing shown. Please log in to see your pricing.

TXSA032L6S2A

TXSA032L6S2A
Call To Order
Condensing unit, water cooled, semi-hermetic compressor, low temp, R404A, 3++ HP, 208-230/1/60
URI Part Number:
TXSA032L6S2A
Vendor Name:
Trenton Refrigeration Products
Length (In.):
32 7/8
Width (In.):
47 3/8
Compressor:
LACB032ECAB
Connection Liquid (In.):
1/2
Connection Suction (In.):
1 1/8
Connection Type:
ODS
Connection Water Inlet (In.):
3/4
Connection Water Outlet (In.):
3/4
Connection Water Type:
ODS
Height (In.):
30
Horsepower:
3 +
MCA (Amps):
19.4
Oil:
Polyol Ester
Oil_short:
POE
Receiver Capacity 90 % Full (Lbs.):
22.0
Refrigerant:
R404A
Sort:
23.0
Voltage:
230/1/60
Shipping Weight (Lbs.):
420

Standard Features

  • Weatherproof electrical control box with compressor contactor and fused control circuit
  • Pre-formed piping
  • Solid mounted accessible semi-hermetic compressor (to 2 HP)
  • Spring mounted accessible semi-hermetic compressor with suction and discharge vibration eliminator (3 HP and over)
  • Suction service valve.
  • Copper tubing secured with cushion clamps
  • Coaxial condenser
  • Receiver with fusible plug and liquid shut off valve
  • Adjustable dual high/low pressure control
  • Each unit subjected to a thorough leak test with helium leak-detectors
  • Units are shipped with helium holding charge

Optional Features

  • Suction and discharge vibration eliminator (to 2 HP)
  • Suction accumulator (with or without boil-out coil)
  • Discharge line check valve
  • Oil separator (with or without oil return filter & solenoid valve)
  • Receiver inlet ball valve
  • Over-sized receiver
  • Sealed liquid line filter drier & sight glass
  • Liquid line ball valve (shipped loose)
  • Insulated suction lines
  • Flex hoses for all pressure controls
  • Liquid line solenoid valve (with standard 230 volt coil) shipped loose
  • Compressor circuit breaker
  • Current sensing relay for use with oil safety control (where applicable)
  • Defrost heater contactor with fuse block
  • Evaporator fan contactor with fuse block
  • Disconnect switch
  • Disconnect fusing
  • Pump down toggle switch
  • Lock out control circuit (liquid solenoid valve with separate HP and LP controls)
  • Time delay relay for compressor
  • Mechanical time clock
  • Electronic time clock
  • Electronic defrost kit
  • Electronic voltage/phase monitor
  • Water regulating valve (shipped loose)