CAL151HMA0A000

CAL151HMA0A000
Condensing unit, air conditioning, 12.5T 208-230/3/60, Single Circuit/Dual Stage R454B
Vendor Name:
Arcoaire
URI Part Number:
CAL151HMA0A000
Vendor Part Number:
CAL151HMA0A000
Length (In.):
45 7/8
Width (In.):
59 3/8
Height (In.):
50 3/8
CFM:
6000
Connection Liquid (In.):
5/8
Connection Suction (In.):
1 3/8
Cooling Capacity (BTUH):
151000
Cooling Efficiency (EER):
11.0
Hertz:
60
Maximum Fuse / Breaker Size (Amps):
60
MCA (Amps):
51
Motor Horsepower:
1/4
Nominal Tons:
12.5
Note 1:
Single Circuit/Dual Stage
Number of Circuits:
1
Phase:
3
Refrigerant:
R454B
Sound Rating Decibels:
82.6
Voltage:
208-230
Prop65:
WARNING: This product can expose you to chemicals including Lead, and Lead compounds, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
  • R-454B refrigerant.
  • Single circuit two-stage cooling capacity control on 072-241 sizes.
  • Dual circuit, three-stage cooling capacity on 123-303 sizes.
  • All model sizes utilize copper tube/aluminum plate fin condenser coils.
  • Cooling operating range up to 125°F (52°C) and down to 35°F (2°C).
  • Meets and exceeds ASHRAE 90.1 energy efficiency levels.
  • Brass suction and liquid line service valves.
  • Fully Hermetic Scroll compressor with crankcase heater.
  • New terminal board facilitating simple safety circuit troubleshooting and simplified control box arrangement. 24-volt 75va control system.
  • High and low pressure switches.
  • Comfort Alert Diagnostic Board
  • Rated in accordance with AHRI Standards 340/360.
  • Designed in accordance with Underwriters’ Laboratories Standard UL 60335-1 and UL 60335-2-40
  • Listed by UL and CUL-Canada
  • Full perimeter base rails with built-in rigging adapters and fork truck slots
  • Pre-painted exterior panels and primer-coated interior panels tested to 500 hours salt spray protection
  • Direct drive permanently lubricated condenser fan motors
  • All units factory run tested
  • Compressors mounted on independent vibration isolators
  • High capacity filter drier is supplied for each circuit. Field installation is required.
Documents