Log in for pricing and inventory.

C161KKD1C

C161KKD1C
Direct spark ignition module, 300 sec recycle time
Voltage :
24
Ignition Attempts (before lockout) :
3
SKU :
C161KKD1C
Branch Pickup Only :
No
Replaces :
BG1100MADL1G
Prepurge Time (Sec.) :
30
Specials :
No
LogoImage :
L/Logo_baso.jpg
Specials Description :
Direct spark ignition module, 300 sec recycle time
Vendor Name:
Baso
Sort :
3.0
Web Description :
Direct spark ignition module, 300 sec recycle time
manufacturerSKU :
C161KKD1C
Contact Rating (Amps) :
2
Weight :
0.75 lb
manufacturerName :
Baso
longDescription :

BASO has designed in timings on various direct spark controls with flame rectification to replace many Johnson Controls, Honeywell, United Technologies, Fenwal, and Robertshaw.
These are microprocessor based controls suited for direct replacement and new applications. Direct spark modules provide ignition sequence, flame monitoring, and safety shutoff for boilers, furnaces, and a variety of other commercial cooking equipment. Direct spark modules are available with various specifications as follows:

  • Single rod (local sense) or dual rod (remote sense) flame sensing
  • 100% shutoff/lockout with none, 5 or 60 minutes continuous retry
  • Trial for ignition 1 or 3
  • Trial times of infinite, 4, 5, 8, 10, 15, 20, 25, 30, 50, 60, 85, 90 and 120 seconds.
  • Pre-purge period of none, 4, 8, 10, 15, 30, 45, 60 seconds or 4 minutes
  • Main burner 400,000 Btu/hr max.
  • Temperature ranges of -40°F to 170°F
  • 24 Volt
  • Recycle time: 300 seconds
    Other models available upon request
URI Part Number:
C161KKD1C
Vendor Part Number:
C161KKD1C
Ignition Trial Time (Sec.):
8
Shipping Weight (Lbs):
0.75
Weight (Lbs):
0.75

BASO has designed in timings on various direct spark controls with flame rectification to replace many Johnson Controls, Honeywell, United Technologies, Fenwal, and Robertshaw.
These are microprocessor based controls suited for direct replacement and new applications. Direct spark modules provide ignition sequence, flame monitoring, and safety shutoff for boilers, furnaces, and a variety of other commercial cooking equipment. Direct spark modules are available with various specifications as follows:

  • Single rod (local sense) or dual rod (remote sense) flame sensing
  • 100% shutoff/lockout with none, 5 or 60 minutes continuous retry
  • Trial for ignition 1 or 3
  • Trial times of infinite, 4, 5, 8, 10, 15, 20, 25, 30, 50, 60, 85, 90 and 120 seconds.
  • Pre-purge period of none, 4, 8, 10, 15, 30, 45, 60 seconds or 4 minutes
  • Main burner 400,000 Btu/hr max.
  • Temperature ranges of -40°F to 170°F
  • 24 Volt
  • Recycle time: 300 seconds
    Other models available upon request
Substitutes