Log in for pricing and inventory.

PP902D1007

PP902D1007
Pneumatic pressure reducing valve, two pressure, submicron filter, 2 gauges
Description :
Two Pressure
LogoImage :
L/Logo_Honeywell.jpg
Web Description :
Pneumatic pressure reducing valve, two pressure, submicron filter, 2 gauges
Weight :
5.7 lb
Branch Pickup Only :
No
Specials :
No
longDescription :

Used to control the pressure of the air delivered to pneumatic control systems. Models available for single-pressure systems or two-pressure systems (day/night or summer/winter) requiring two independently regulated pressure settings. Dual pressure units switch from the lower setting to a higher setting when main air is applied to the pilot port. Models also available including a sub-micron filter assembly and pressure gauges.

  • Built-in adjustable safety relief valve for limiting downstream pressure
  • Inlet pressure: 45-150 psi
  • Outlet pressure: 0-25 psi, factory 18 psi
  • Safety relief pressure: 12-25 psi, factory 22-25 psi
  • Secondary pressure: 0-5 psi above primary setting
    Factory set: 4.5 psi
manufacturerName :
Honeywell
Factory Set Defaults :
4.5 psi
Sort :
3.0
SKU :
PP902D1007
Vendor Name:
Honeywell
manufacturerSKU :
PP902D1007/U
Inlet Pressure (psi) :
45 - 150
Specials Description :
Pneumatic pressure reducing valve, two pressure, submicron filter, 2 gauges
URI Part Number:
PP902D1007
Vendor Part Number:
PP902D1007/U
Shipping Weight (Lbs):
5.70
Prop65:
No
Weight (Lbs):
5.70

Used to control the pressure of the air delivered to pneumatic control systems. Models available for single-pressure systems or two-pressure systems (day/night or summer/winter) requiring two independently regulated pressure settings. Dual pressure units switch from the lower setting to a higher setting when main air is applied to the pilot port. Models also available including a sub-micron filter assembly and pressure gauges.

  • Built-in adjustable safety relief valve for limiting downstream pressure
  • Inlet pressure: 45-150 psi
  • Outlet pressure: 0-25 psi, factory 18 psi
  • Safety relief pressure: 12-25 psi, factory 22-25 psi
  • Secondary pressure: 0-5 psi above primary setting
    Factory set: 4.5 psi