Log in for pricing and inventory.

A11B1

A11B1
Temperature control, freezestat, 35 to 45°F, 8°F fixed differential, SPST open low, 8 Amps 240 V
Contact Rating (Amps) :
8
Switch :
SPST—open low
manufacturerSKU :
A11B-1C
Branch Pickup Only :
No
manufacturerName :
Johnson Controls
Element :
20' of 1/8 O.D. tubing, 4' capillary
LogoImage :
L/Logo_JohnsonControls.jpg
SKU :
A11B1
Web Description :
Temperature control, freezestat, 35 to 45°F, 8°F fixed differential, SPST open low, 8 Amps 240 V
longDescription :

The A11 Series low temperature cutout controls incorporate a 20 foot long, vapor charged, sensing element. These controls react to the coldest 18 inch section of the control sensing element.
These controls are suitable for monitoring the face temperature of hot water coils for freeze protection. The most common application for these controls is as a low temperature cutout for coils and/or pipe liquid sensing

  • Element: 20' of 1/8 O.D. tubing, 4' capillary
  • Switch: SPST—open low
Specials :
No
Differential :
8°F, Fixed
Sort :
2.0
Vendor Name:
Johnson Controls
Weight :
1.8 lb
Specials Description :
Temperature control, freezestat, 35 to 45°F, 8°F fixed differential, SPST open low, 8 FLA 240 V
URI Part Number:
A11B1
Vendor Part Number:
A11B-1C
Length (In.):
10.40
Width (In.):
4.60
Height (In.):
2.70
Ambient Temperature:
0 to 140°F
Shipping Height (In.):
2.438
Shipping Length (In.):
10.125
Shipping Width (In.):
4.313
Shipping Weight (Lbs):
1.80
Prop65:
WARNING: This product contains chemicals known to the State of California to cause cancer and reproductive harm. For more information go to www.P65Warnings.ca.gov
Weight (Lbs):
1.80

The A11 Series low temperature cutout controls incorporate a 20 foot long, vapor charged, sensing element. These controls react to the coldest 18 inch section of the control sensing element.
These controls are suitable for monitoring the face temperature of hot water coils for freeze protection. The most common application for these controls is as a low temperature cutout for coils and/or pipe liquid sensing

  • Element: 20' of 1/8 O.D. tubing, 4' capillary
  • Switch: SPST—open low
Documents