A70GA1

A70GA1
Temperature control, freezestat, alarm, 15 to 55°F, 5°F fixed differential, 20' capillary, open low main switch, close low aux. switch, 8 (main) 3 (aux.) Amps 240 V
Branch Pickup Only :
No
longDescription :

The A70G, A70H, and A70K have a four-wire, two circuit contact block that contains two isolated sets of contacts.
The contacts are designed so that when the main contact opens, the auxiliary contact closes.
Typical applications would include energizing an indicator light upon low temperature cutout on a ventilating system.
Use as freezestat.
A70GA1/A70HA1 only
Low cutout stop is set and sealed at 35°F (1.6°C). Control responds only to the lowest temperature along any 1' of entire 20' element or bellows cup

Differential :
5, Fixed
LogoImage :
L/Logo_JohnsonControls.jpg
Web Description :
Temperature control, freezestat, alarm, 15 to 55°F, 5°F fixed differential, 20' capillary, open low main switch, close low aux. switch, 8 (main) 3 (aux.) Amps 240 V
Note 1 :
Low cutout stop is set and sealed at 35°F (1.6°C). Control responds only to the lowest temperature along any 1' of entire 20' element or bellows cup.
manufacturerSKU :
A70GA-1C
Bulb (In.) :
1/8 O.D. Tubing
Weight :
2.4 lb
Specials :
No
Sort :
1.0
manufacturerName :
Johnson Controls
SKU :
A70GA1
Specials Description :
Temperature control, freezestat, alarm, 15 to 55°F, 5°F fixed differential, 20' capillary, open low main switch, close low aux. switch, 8 (main) 3 (aux.) FLA 240 V
Vendor Name:
Johnson Controls
URI Part Number:
A70GA1
Vendor Part Number:
A70GA-1C
Length (In.):
8.30
Width (In.):
6.40
Height (In.):
2.60
Auxiliary Switch:
Close Low
Capillary Length:
20'
FLA Auxiliary:
3
FLA Main:
8
Switch Main:
Open Low
Shipping Height (In.):
2.5
Shipping Length (In.):
8.125
Shipping Width (In.):
6.25
Shipping Weight (Lbs):
2.40
Prop65:
WARNING: This product contains chemicals known to the State of California to cause cancer and reproductive harm. For more information go to www.P65Warnings.ca.gov
Weight (Lbs):
2.40

The A70G, A70H, and A70K have a four-wire, two circuit contact block that contains two isolated sets of contacts.
The contacts are designed so that when the main contact opens, the auxiliary contact closes.
Typical applications would include energizing an indicator light upon low temperature cutout on a ventilating system.
Use as freezestat.
A70GA1/A70HA1 only
Low cutout stop is set and sealed at 35°F (1.6°C). Control responds only to the lowest temperature along any 1' of entire 20' element or bellows cup