The website requires your browser to enable cookies in order to login.
Please enable cookies and reload this page.
The A70G, A70H, and A70K have a four-wire, two circuit contact block that contains two isolated sets of contacts.
The contacts are designed so that when the main contact opens, the auxiliary contact closes.
Typical applications would include energizing an indicator light upon low temperature cutout on a ventilating system.
Use as freezestat.
A70GA1/A70HA1 only
Low cutout stop is set and sealed at 35°F (1.6°C). Control responds only to the lowest temperature along any 1' of entire 20' element or bellows cup