Designed for long, trouble-free service in even the most demanding applications.
Each standard stock receiver conforms to UL, CSA or ASME requirements for 450 psi maximum working pressure. Models with an internal diameter under 6" are UL Listed; all larger models are made according to ASME code and tagged appropriately.
All pumpdowns are calculated at 80% capacity, R22 liquid.
- Due to the high working pressures of R410A. any receiver must be customized to conform to ASME construction. Please contact branch/customer service for more information
- Working pressure: 450 psi
Pumpdowns are calculated at 80% of receiver volume, R22
For other refrigerants multiply listed value by factor below
R12 x 1.10
R134a x 1.01
R404A x 0.89
R507 x 0.88