Log in for pricing and inventory.

THP243MTT5A

THP243MTT5A
Call To Order
Unit cooler, walk-in, 6 FPI, hot gas defrost, 3-pipe with electric heater, 243000 BTUH +25°F ET, 575/3/60 volt, 57-9/32" H x 40-1/2" W x 187" L
Heater Amps :
14.2
Voltage :
575/3
CFM :
34800
Motor Maximum Fuse (Amps) :
15
Engineered Items :
Yes
LTL Only :
Yes
LogoImage :
L/Logo_TRENTON.jpg
Branch Pickup Only :
No
Number of Motors :
4
Specials Description :
Unit cooler, walk-in, 6 FPI, hot gas defrost, 3-pipe with electric heater, 243000 BTUH +25?F ET, 575/3/60, 57 9/32" H x 40 1/2" W x 187" L
Motor FLA :
9.2
Motor MCA :
9.8
Vendor Name:
Trenton Refrigeration Products
Sort :
111.0
Web Search :
evaporator walkin walk in
Fins/Inch :
6
Motor Horsepower :
1.5
longDescription :

Standard Features

  • Heavy gauge textured aluminum cabinet with galvanized steel hangers, support channels and end plates
  • Hinged access panels with removable hinge pins and captive fasteners.
  • Hinged drain pan with removable hinge pins
  • Rugged heavy-gauge galvanized steel rail motor mount / support.
  • Stackable design
  • Schrader fitting and external equalizer line.
  • Factory installed solenoid valve wire harness
  • Unit shipped upright for convenient handling and quick installation.

Optional Features

  • Factory mounted TX valve, solenoid valve and thermostat
  • Throw boosters
  • Insulated drain pan
  • TEFC motors
  • Optional fin spacing
  • Optional fin materials
  • Optional coil coating


Available in sizes from 67,900 to 271,000 BTUH.

  • Adjustable defrost termination thermostat
  • Heater safety thermostat (on models with heaters)
  • Fixed fan delay thermostat
    Standard units are equiped with an electric heater (hot gas drain pan loop optional) and are suitable for three pipe or reverse cycle applications
  • Maximum fuse is for heater circuits only; motor fusing listed separately
    Replace (*) with letter code to completely specify required configuration
    T = 3 Pipe with Electric Heater
    G = Reverse Cycle with Electric Heater
Heater MCA :
17.7
Maximum Fuse / Breaker Size (Amps) :
20
Specials :
No
Weight :
1,664.0 lb
manufacturerName :
Trenton Refrigeration Products
SKU :
THP243MTT5A
Web Description :
Unit cooler, walk-in, 6 FPI, hot gas defrost, 3-pipe with electric heater, 243000 BTUH +25°F ET, 575/3/60 volt, 57-9/32" H x 40-1/2" W x 187" L
Heater Watts :
14100
Connection Type :
ODS
Motor Type :
ODP
URI Part Number:
THP243MTT5A
Length (In.):
187
Width (In.):
40 1/2
Height (In.):
57 9/32
Connection Size Inlet (In.):
1 3/8
Connection Suction (In.):
2 5/8
Shipping Weight (Lbs):
1664.00
Prop65:
WARNING: This product can expose you to chemicals including Lead, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weight (Lbs):
1664.00

Standard Features

  • Heavy gauge textured aluminum cabinet with galvanized steel hangers, support channels and end plates
  • Hinged access panels with removable hinge pins and captive fasteners.
  • Hinged drain pan with removable hinge pins
  • Rugged heavy-gauge galvanized steel rail motor mount / support.
  • Stackable design
  • Schrader fitting and external equalizer line.
  • Factory installed solenoid valve wire harness
  • Unit shipped upright for convenient handling and quick installation.

Optional Features

  • Factory mounted TX valve, solenoid valve and thermostat
  • Throw boosters
  • Insulated drain pan
  • TEFC motors
  • Optional fin spacing
  • Optional fin materials
  • Optional coil coating


Available in sizes from 67,900 to 271,000 BTUH.

  • Adjustable defrost termination thermostat
  • Heater safety thermostat (on models with heaters)
  • Fixed fan delay thermostat
    Standard units are equiped with an electric heater (hot gas drain pan loop optional) and are suitable for three pipe or reverse cycle applications
  • Maximum fuse is for heater circuits only; motor fusing listed separately
    Replace (*) with letter code to completely specify required configuration
    T = 3 Pipe with Electric Heater
    G = Reverse Cycle with Electric Heater
Documents