Log in for pricing and inventory.

TLV180HES2

TLV180HES2
Call To Order
Unit cooler, walk-in, low velocity, hot gas defrost, 3-pipe, 18000 BTUH 20°F ET, 208-230/1/60 volt, 14-15/16" H x 28-1/8" W x 92-7/8" L
Engineered Items :
Yes
LTL Only :
Yes
Weight :
295.0 lb
LogoImage :
L/Logo_TRENTON.jpg
Branch Pickup Only :
No
Voltage :
208-240/1
longDescription :

The TLV hot gas defrost low velocity unit coolers can be applied in lower temperature 28°F to 34°F rooms. The hot gas defrost units include corrosion proof incoloy sheathed heaters on individual drain pan assemblies preventing re-freezing of condensate water during defrost cycles. Factory installed side outlet distributor and Thermodisc type fan delay thermostats are standard. Check valves are supplied loose for TX valve by-pass. Units are suitable for reverse cycle, three pipe, and ThermoSaver™ hot gas defrost applications.
HE= 3 Pipe Defrost
RE= Reverse Cycle Defrost
TE= Thermosaver Defrost

Vendor Name:
Trenton Refrigeration Products
Heater Watts :
820
Motor Type :
PSC
Specials Description :
Unit cooler, walk-in, low velocity, hot gas defrost, 3-pipe, 18000 BTUH 20°F ET, 208-230/1/60, 14 15/16" H x 28 1/8" W x 92 7/8" L
Web Search :
evaporator walkin walk in
CFM :
2530
manufacturerName :
Trenton Refrigeration Products
Specials :
No
Comments :
3 Pipe Defrost, Electric Heated Drain Pan
Web Description :
Unit cooler, walk-in, low velocity, hot gas defrost, 3-pipe, 18000 BTUH 20°F ET, 208-230/1/60 volt, 14-15/16" H x 28-1/8" W x 92-7/8" L
SKU :
TLV180HES2
Heater Amps :
3.6
Sort :
28.0
Number of Motors :
3
Connection Type :
ODS
URI Part Number:
TLV180HES2
Length (In.):
92 7/8
Width (In.):
28 1/8
Height (In.):
14 15/16
Connection Size Inlet (In.):
1/2
Connection Suction (In.):
1 1/8
MCA (Amps):
2.7
Shipping Weight (Lbs):
295.00
Prop65:
WARNING: This product can expose you to chemicals including Lead, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weight (Lbs):
295.00

The TLV hot gas defrost low velocity unit coolers can be applied in lower temperature 28°F to 34°F rooms. The hot gas defrost units include corrosion proof incoloy sheathed heaters on individual drain pan assemblies preventing re-freezing of condensate water during defrost cycles. Factory installed side outlet distributor and Thermodisc type fan delay thermostats are standard. Check valves are supplied loose for TX valve by-pass. Units are suitable for reverse cycle, three pipe, and ThermoSaver™ hot gas defrost applications.
HE= 3 Pipe Defrost
RE= Reverse Cycle Defrost
TE= Thermosaver Defrost

Documents