Programmer burner control, interrupted pilot, replaces Fireye M
Vendor Name:
Honeywell
URI Part Number:
R7120M1019
Vendor Part Number:
R7120M1019
Description:
Burner Control Module, Interrupted
Shipping Weight (Lbs.):
3
Replaces:
Fireye M Interrupted
Prop65:
No
Microprocessor-based integrated burner controls. It is a plug in replacement of Fireye M series using existing Fireye wiring subbase
  • Functions provided by the R7120M include automatic burner sequencing, flame supervision, system status indication, system or self-diagnostics and troubleshooting.
  • Require ST7800 Purge Timer and appropriate R78XX Amplifier to complete the replacement.
  • PrePurge: Determined by ST7800A Purge Timer Card
  • PostPurge: programmed with S7800A1142 display
  • 4 or 10 second pilot flame establishing period