Log in for pricing and inventory.

034N0081

034N0081
Discharge bypass valve, adjustable, external equalizer, 1/2" male flare, 0 to 85 psi
Connection Type :
MFL
LogoImage :
L/Logo_danfoss.jpg
Capacity (Tons) :
6.7
SKU :
034N0081
Vendor Name:
Danfoss
Branch Pickup Only :
No
Maximum Differential Pressure :
260
Specials Description :
Discharge bypass valve, adjustable, external equalizer, 1/2" male flare, 0 to 85 psi
Web Description :
Discharge bypass valve, adjustable, external equalizer, 1/2" male flare, 0 to 85 psi
Weight :
5.0 lb
Adjustment Range (psi) :
0 to 85
Specials :
No
Maximum Operating Pressure (psi) :
400.0
Maximum Over Pressure :
450
Sort :
1.0
manufacturerSKU :
034N0081
longDescription :
  • Superior control accuracy
  • Provides protection against too low an evaporator temperature
  • Direct connection to system suction line
  • For use with CFC, HCFC and HFC refrigerants
  • Regulation range: 0 to 85 psig
  • Factory setting: 5.8 psig
  • Maximum working pressure MWP : 400 psig
  • Maximum differential pressure: 260 psig
  • Maximum test pressure: 450 psig
  • Maximum media temperature: 285°F
  • Minimum media temperature:-50°F
  • 1/4" flare pilot connection
  • Rated capacity R407C, minimum suction temperature: 15°F, condensing temperature: 100°F, expansion valve superheat: 7°F
    Approvals: UL listed, file SA7200 ; CSA approved
manufacturerName :
Danfoss
URI Part Number:
034N0081
Vendor Part Number:
034N0081
Length (In.):
11.00
Width (In.):
9.00
Height (In.):
4.00
Connection Size (In.):
1/2
Country of Origin:
DE
Maximum Media Temperature ( Deg. F):
285
Minimum Media Temperature ( Deg. F):
-50
Overall Height (In.):
7.00
Shipping Weight (Lbs):
5.00
Prop65:
WARNING: This product can expose you to chemicals including Lead, and Lead compounds, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weight (Lbs):
5.00
  • Superior control accuracy
  • Provides protection against too low an evaporator temperature
  • Direct connection to system suction line
  • For use with CFC, HCFC and HFC refrigerants
  • Regulation range: 0 to 85 psig
  • Factory setting: 5.8 psig
  • Maximum working pressure MWP : 400 psig
  • Maximum differential pressure: 260 psig
  • Maximum test pressure: 450 psig
  • Maximum media temperature: 285°F
  • Minimum media temperature:-50°F
  • 1/4" flare pilot connection
  • Rated capacity R407C, minimum suction temperature: 15°F, condensing temperature: 100°F, expansion valve superheat: 7°F
    Approvals: UL listed, file SA7200 ; CSA approved