Log in for pricing and inventory.

LCE6160BEWMC6B

LCE6160BEWMC6B
Unit cooler, walk-in, 6 FPI, electric defrost, low profile, pre-assembled, 16000 BTUH -20°F, 208-230/1/60 volt, 14-3/4" H x 14-15/16" W x 77-1/2" L
Engineered Items :
Yes
LTL Only :
Yes
Branch Pickup Only :
No
LogoImage :
L/Logo_LARKIN.jpg
Voltage :
208-240/1
Number of Motors :
4
Motor Type :
ECM
Web Search :
evaporator walkin walk in
Fins/Inch :
6
Application :
Low Temp
SKU :
LCE6160BEWMC6B
Heater Watts :
3600
Web Description :
Unit cooler, walk-in, 6 FPI, electric defrost, low profile, pre-assembled, 16000 BTUH -20°F, 208-230/1/60 volt, 14-3/4" H x 14-15/16" W x 77-1/2" L
Specials :
No
longDescription :

New design allows easy front access to electrical and refrigeration components. More volume in electrical cavity for component installation. Heaters are attached to coil... no need to disconnect from electrical board to drop drain pan.

  • For applications -20°F and above
  • Width: 15" (16 5/8" at refrigerant connections)
  • Height: 15" (16" at drain spud)
  • BTU 10°F TD, -20°F SST


  • Pre-assembled: expansion valve, solenoid valve and temperature control are mounted and wired.
  • Glycol models available
Vendor Name:
Larkin
manufacturerName :
Larkin
Heater Amps :
15.7
manufacturerSKU :
LCE6160BEWMC6B
Weight :
84.0 lb
Sort :
23.0
Specials Description :
Unit cooler, walk-in, 6 FPI, electric defrost, low profile, pre-assembled, 16000 BTUH -20°F, 208-230/1/60, 14 3/4" H x 14 15/16" W x 77 1/2" L
CFM :
2600
Connection Type :
ODS
URI Part Number:
LCE6160BEWMC6B
Vendor Part Number:
LCE6160BEWMC6B
Length (In.):
77.5
Width (In.):
15
Height (In.):
15
Connection Size Inlet (In.):
1/2
Connection Suction (In.):
1 1/8
Shipping Weight (Lbs):
84.00
Prop65:
WARNING: Cancer and Reproductive Harm- For more information go to www.P65Warnings.ca.gov
Weight (Lbs):
84.00

New design allows easy front access to electrical and refrigeration components. More volume in electrical cavity for component installation. Heaters are attached to coil... no need to disconnect from electrical board to drop drain pan.

  • For applications -20°F and above
  • Width: 15" (16 5/8" at refrigerant connections)
  • Height: 15" (16" at drain spud)
  • BTU 10°F TD, -20°F SST


  • Pre-assembled: expansion valve, solenoid valve and temperature control are mounted and wired.
  • Glycol models available
Documents